Call us on  03 8806 8356

Home » Delta UPS Solutions » Delta UPS – Amplon Family » RT Series, Single Phase, 1/2/3 kVA

RT Series, Single Phase, 1/2/3 kVA

Reliable power with greater energy-saving features

The Amplon RT 1-3kVA series is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. The Amplon RT 1-3kVA series features an output power factor of 0.9 and best-in-class AC-AC efficiency up to 94% resulting in greater energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.

Applications: Server, Telecom, Industrial, Network, VoIP, Storage, Medical

 

Availability

  • True online double-conversion topology and zero transfer time to battery ensure high reliability.
  • Watch-dog design of DSP (Digital Signal Processor) increases reliability.
  • Cold-start capability provides temporary battery power when the utility power is out.
  • Fan failure detection alerts users to failed fans.
  • Hot swappable batteries ensure continuous operation even when batteries are being replaced.
  • Optional external battery pack for easy scaling of longer backup time.
  • Operation temperature tolerance up to 50°C ensures critical loads’ continuity
  • High output power factor 0.9 provides more real power to critical loads.


Green & Low TCO

  • High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 5%) save upstream investment.
  • Up to 94% AC-AC efficiency and 97% efficiency in ECO mode result in marked energy cost savings.
  • Wide input voltage range reduces the chance of using the battery and extends battery life.
  • Intelligent battery management sustains battery life and performance.
  • Fan speed control by load level maximizes efficiency and reduces audible noise.


Flexibility

  • Load segment control allows less-critical loads to be disconnected during blackouts and saves battery runtime for important loads.
  • Convertible rack and tower configuration in 2U size cabinet.
  • Excellent local communications through rotatable LCD display.
  • Intelligent management software connectivity via RS232 or USB port.
Model: RT-1K / RT-2K / RT-3K

Power Rating
[RT-1K]: 1kVA / 0.9kW
[RT-2K]: 2kVA/ 1.8kW
[RT-3K]: 3kVA/ 2.7kW
 
Input
Nominal Voltage: 200*/208*/220/230/240 Vac
Voltage range:
175 ~ 280 Vac (full load)
120 ~ 175 Vac (70 ~ 100% load)
Frequency: 40 ~ 70 Hz
Power Factor: > 0.99 (full load)
Current Harmonic Distortion: < 5%
 
Output
Power Factor: 0.9
Voltage: 200*/208*/220/230/240 Vac
Voltage Regulation: ± 1% (linear load)
Frequency: 50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion: < 2% (linear load)
Overload Capability
< 105%: Continuous
105% ~ 125%: 1 minute
125% ~ 150%: 15 seconds
Receptacle
[RT-1K]: IEC C13 x 6
[RT-2K/3K]: IEC C13 x 6, IEC C19 x 1
 
Efficiency
AC-AC
[RT-1K]: 90%
[RT-2K/3K]: Up to 94%
ECO Mode
[RT-1K]: 96%
[RT-2K/3K]: Up to 97%
 
Battery
Battery Voltage
[RT-1K]: 24 Vdc
[RT-2K]: 48 Vdc
[RT-3K]: 72 Vdc
Typical Backup Time**
[RT-1K]: 6.5 minutes
[RT-2K/3K]: 7 minutes
Charge Current
[RT-1K]: 1.5A
[RT-2K/3K]: 2A
Recharge Time: 3 hours to 90%
Audible Noise:
[RT-1K]: < 40 dBA
[RT-2K]: < 43 dBA
[RT-3K]: < 46 dBA
Display: LCD display and LED indicators
Communication Interfaces: SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1
Conformance: EN 62040-1, CE, TISI, RCM, EAC
 
Dimensions (W x D x H)
UPS
[RT-1K]: 440 x 335 x 89 mm
[RT-2K]: 440 x 432 x 89 mm
[RT-3K]: 440 x 610 x 89 mm
External Battery Pack
[RT-1K]: 440 x 335 x 89 mm
[RT-2K]: 440 x 432 x 89 mm
[RT-3K]: 440 x 610 x 89 mm
 
Weight
UPS
[RT-1K]: 12 kg
[RT-2K]: 18 kg
[RT-3K]: 28 kg
External Battery Pack
[RT-1K]: 15 kg
[RT-2K]: 27 kg
[RT-3K]: 44 kg
 
Environment
Operating Temperature: 0 ~ 50°C***
Relative Humidity: 5% ~ 95% (non-condensing)
 
* When the UPS is de-rated to 90% of its capacity.
** When the total load reaches 75%.
*** 40 ~ 50°C with 80% de-rating.

All specifications are subject to change without prior notice.

Run Time

Power RatingBatteryRun time at different load (mins)
25%50%75%100%
1 kVAInternal27.011.26.23.8
External x 1100.048.229.820.2
External x 2174.387.155.739.1
External x 3248.7126.482.258.6
2 kVAInternal27.911.46.33.9
External x 1102.948.830.120.6
External x 2179.188.156.339.9
External x 3255.4127.882.959.7
3 kVAInternal33.114.27.95.1
External x 1119.258.436.325.2
External x 2206.3104.466.947.8
External x 3293.6150.697.970.9